If you look up through rainscreen cladding you may see all the way up, past a number of cavity fire barriers. This see-through gap is the path of free-flowing air that keeps the cavity dry. In fire, the see-through gap becomes filled with expanded intumescent material – after a while that is, after the passing of fire. Novel products now always resist fire.
Do ventilating cavity barriers work as intended?
When tested with room fires that heat the air slowly and do not produce flames until 5 minutes after ignition, they work. When tested with sudden direct flaming, they certainly do not. During investigations and joint tests by the ABI and FPA following the Grenfell fire, it became apparent that something may be seriously wrong. Do they work in everyday slow fire exposures and will they fail in catastrophic fires?
There are two fundamentally different types of fire-resistance-rated cavity barriers that are ventilating: the traditional design is termed ‘open’, which allows flames to pass before sealing, but more recent designs are termed ‘open state fire resistance rated’ and block flames immediately while still in the open state, before sealing up as well. Sealing is typically complete between 50 seconds and 5 minutes, depending on exposure.

The ‘breaking of window’ fire that ignites cladding is the common scenario for facade testing. This means sudden direct flame exposure at cavity barriers may penetrate them in seconds (solid combustibles ignite at 1–3 seconds up-wards). As fires escalate at great speed, such as observed at Grenfell, there is no time for the intumescent material to expand and seal. This is not a standard room fire but rather a flame attack against cavity barriers in the open state.
If the combustible decor cladding at Grenfell was changed to a non-combustible variety, it still may not have prevented the furious upward spread of fire. It appears that if the most common design of ventilating cavity barriers were installed at Grenfell, they would still have failed because they were never tested by realistic fire exposure.
Test methods inadequate
How is it possible to allow rainscreen cavity barriers to be tested using slow room (enclosure) fire furnace tests? The fire growth of those tests allows flames to pass for the first 5 minutes, and the fires are barely up to flame temperature even at 5–6 minutes after ignition. Most likely, this was accepted as the best one could do 50 years ago, and at the time open-state fire resistance against direct flame was not possible. However, recent European and US product designs have led to open-state-fire-resistance-rated cavity barriers. That progress is recognised in fire codes and specification standards in the US and France. Since 2013, dedicated test methods and prescriptive solutions have been published. They now rely on open-state-fire-resistance-rated cavity barriers. In fact, the first product of this kind was designed and manufactured in England in 2003. It is marketed in EU mainland member states but, strangely, is yet to be sold within UK itself.




Revelations in 2018
The recent joint report by the ABI, FPA and RISC Authority following the Grenfell catastrophe got to grips with this. They carried out probing tests that verified the rationale of the US and French test methods and have recommended to the Grenfell Inquiry and to BSI that the full-scale test method for facades, BS 8414, be reviewed on this basis. The report further proved that compartmentation of cladding cavities is breached by common non-fire-rated wall vents and that the chimney effect of these cavities is not properly addressed by the current BS 8414.
All risks covered
Yet another issue with traditional ventilating cavity barriers is that they may fail when cladding moves due to wind pressure or becomes warped by fire. The intumescence may not expand properly to fill a gap as it widens, either due to insufficient intumescent material or because it has become brittle, loose or dropped out. Yet another issue is wrap-around plastics, which melt, ignite and drip. This may in turn ignite other combustibles or the top plastics of cavity barriers below. In some regions, fires in attics of wooden buildings or wildfires expose wind-borne embers to other buildings that may have rain-screen cladding. Embers are also a threat as they may drop down into or be pulled up inside cavities by the chimney effect, thereby bypassing barriers unless they are ember resistant.
After decades of research and learning from real fires, all of these drawbacks of old are now mitigated. The most recent products are standing by, awaiting updates to test methods and code requirements.
Non-UK developments on see-trough cavity barriers
It was decided in North America to dedicate a new test method to direct flame exposure of open-state elements (vented construction) during the 0–5-minute period. This became the ASTM E2912 Standard. The test method for vents exposed to wildfire adopted that method, ASTM E2886. In Europe CEN decided to add a similar method to both new EN 1364-5 and pr1364-6 Standards. In France a guide has been issued that explains how to apply open-state fire-resistance vents in facades and refers to ASTM 2912 (Bois construction et propagation du feu par les façades En application de l’Instruction Technique 249 01/02/2017).
What is meant by vents having see-through flame protection?
You see flame and you feel luke-warm gas escaping through the open vent. Still, neither flame nor hot gas will ignite newspaper and cotton items on the surface. So, what is going on here? Answer: You are encountering the magic of an open-state fire-resistant vent. That is a vent or ventilating cavity barrier that will never spread fire.
Fire resistance for the open state of vents can be accomplished in numerous ways by applying baffles, labyrinths or long and narrow pipes. But they are generally bulky, expensive or offer low effective venting area. The most recent fully passive technology exploits the quenching gap effect combined with multiple heat-sink methods and geometries plus intumescent. The magic is not in these individual details but in the clever combined performance.
Contrary to traditional open-state ventilating cavity barriers the new designs block direct flame or sustained fire for 30, 60, 90 minutes or more. Typical ratings are EI 30 (E30/I30). Traditional designs are typically written E/I 30/15 or E/I 5-30/5-15 since the current test standards and classification of EI do not consider failures during the first 0–5 minutes of test. Incidentally, this is the open-state period (before becoming fully sealed by expanded intumescent) which is when cavity barriers are most vulnerable to fire transfer.
The new products stop fires instantly and throughout their rated period.